The location, source, and concentration of H2S when detected are important in determining the potential H2S hazard condition and resulting actions. The following guidelines address the various locations and activities where H2S might be encountered.
The ship's officers provide 24-hr monitoring of the central H2S alarm panel while operating on a H2S site. When an alarm goes off on this panel, it is the responsibility of the ship's officer to take the appropriate action.
Table T2 is provided for guidance only and may be modified by the offshore installation manager and the ship's master as the situation and experience with the local H2S environment dictates.
Alarm area
|
Action
|
Core laboratory | Notify H2S safety technician |
Core receiving platform* | Notify H2S safety technician |
Core entry | Notify H2S safety technician |
Core catcher bench* | Notify H2S safety technician |
Lower 'tween deck landing | Notify laboratory officer and investigate |
Hold 'tween deck landing | Notify laboratory officer and investigate |
Fresh air intake plenum* | Shut down intake fans and investigate |
Rig floor* | Notify core technician |
Multiple alarms on "*" detectors above | Sound alarm using coded bell signals and announce H2S EMERGENCY via public address system |
Possible blowout! |
|
The two core technicians are responsible for monitoring H2S levels on the rig floor during their shift to provide 24-hr coverage. The core technician works under the authority of the offshore installation manager and the night tool pusher. Note that in the following instructions, references to the offshore installation manager include the night tool pusher or other offshore installation manager designee.
The H2S safety technicians are two marine specialists assigned the responsibility for monitoring H2S levels on the core-receiving platform and in the core laboratory. There is an H2S safety technician assigned to each shift for 24-hr coverage. The H2S safety technicians work under the authority of the laboratory officer and assistant laboratory officer.
The technicians operating these tools are responsible for monitoring any H2S that maybe trapped inside the tool.
The following guidelines apply when retrieving a core barrel or other tools deployed through the drill string.
The core technician is responsible for monitoring H2S levels on the drill floor with a portable detector. The drill pipe opening (while opening), upper drill string connection, top of inner core barrel, and bottom of core catcher sub are areas that should be monitored.
Table T3 gives guidance on who must wear a BA before opening the drill string and measuring the H2S levels.
H2S hazard
condition |
Core
technician |
Rig floor
crew |
Driller
(driller's shack) |
Watch | No | No | No |
Alert | No | No | No |
Danger | Yes | Yes | No |
Emergency | Yes | Yes | Yes |
When H2S is detected at the drill pipe, the following procedures must be implemented, depending on the concentration detected and how it was measured.
After a positive reading, the core technician notifies the offshore installation manager, who may change the H2S hazard condition to ALERT.
Although unlikely, a set of circumstances could occur that would cause an H2S blowout to discharge gas up the drill string. The first sign that this situation is occurring would be backflow when the drill string is opened. There are many situations other than a blowout that can cause backflow, but while drilling in an environment where H2S is present the following steps should be taken if backflow is detected unless otherwise instructed by the offshore installation manager:
The core technician is responsible for monitoring H2S levels on the drill floor with a portable detector. The bottom of the core catcher sub and bottom of the core barrel (after removing the core catcher) should be monitored.
Table T4 provides guidance to determine who must wear a BA before the removing the core catcher and measuring the H2S levels.
H2S hazard condition
|
Core
technician |
Rig floor
crew |
Core
handlers |
Watch (potential) | No | No | No |
Alert (1–19 ppm) | No | No | No |
Danger (20–49 ppm) | Yes | Yes | Yes |
Emergency (>50 ppm) | Yes | Yes | Yes |
If H2S is detected from the core barrel, the following procedures are implemented.
The H2S safety technician is responsible for monitoring H2S levels on the core-receiving platform with a portable detector. The core (vent holes and cut ends), 12 in above the core, the core catcher, and core storage racks (outside the laboratory) should be monitored.
When H2S is detected above the core liner during venting, the following procedures are followed.
Clathrates (gas hydrates) are crystalline substances composed principally of three-dimensional cages of water in which various gases (e.g., CH4 and H2S) can enter and stabilize the structure. At room temperature and pressure, a clathrate will disassociate, releasing a volume of H2S gas that can be greater than the original volume of the clathrate.
If a clathrate is recovered from a site where H2S is expected, the following steps should be taken:
An H2S clathrate may only be brought into the laboratory in a sealed pressure container. Liquid N2 dewars holding H2S clathrates are stored outdoors, away from supply ventilations and sources of ignition, and are marked with warning signs.
The marine specialists and the H2S safety technicians are responsible for monitoring H2S levels in the core laboratory with a portable detector. Core storage racks (inside the laboratory), air in the core splitting room, the cut surface of split cores after splitting, and the cut surface of split cores while laying out in the core laboratory are monitored.
While cores are waiting to be split or measured on the multisensor track (MST), they continue to warm up and may possibly resume degassing. Should this happen, the marine specialists remeasure the H2S levels. If the H2S level is <10 ppm, the core may remain in the laboratory. If it is >10 ppm, the core is removed from the laboratory until it can be sealed as mentioned in the previous section. Warning: cores that are no longer actively emitting H2S may release additional H2S during the core splitting process (especially if the super saw is used). The H2S levels from split cores are often greater than the levels measured in the whole round.
Prior to splitting cores two BAs must be available and ready for use. There must be at least two marine specialists in the splitting room when a core is split. During the splitting process the H2S levels are continuously monitored with a handheld detector. If the H2S level in the splitting room is >20 ppm, core splitting stops and the two the marine specialists cutting the core put on their BAs; all others leave the room.
Cores may be taken back outside the laboratory to finish degassing or left on the splitting table, covered, and vented using the flexible exhaust duct provided in the splitting room (Fig. F1). Core halves do not leave the splitting room until all signs of active degassing have stopped and the remaining H2S concentration from the core is <10 ppm. Note: some individuals may be very sensitive to low levels of H2S. The 10-ppm level may have to be set lower for these individuals or a BA provided for them to use.
All D-tubes and core boxes holding cores that have emitted H2S are tagged with H2S warning labels. H2S warning signs are placed on core refrigerators where these cores are stored.
To keep the air fresh in the core laboratory,
When H2S is detected in the core Laboratory, the following procedure must be followed.
Because each tool is unique, it is the responsibility of the technician operating the tool to carefully check for H2S in sampling chambers or for H2S trapped inside the tool's housing.
If the H2S hazard condition is ALERT (1–19 ppm) or higher, then the tool's sampling chambers are vented outside or in a controlled manner such that there is no chance of H2S escaping into the work area. The laboratory officer will approve such controls prior to tool's operation.
Should the technician suspect the tool's housing has been compromised and may possibly contain fluids or materials with H2S, the technician opens the housing in an open-air location.
If samples collected are transferred to another container, that container must have an H2S warning tag (see "Pressure Core Samplers, Autoclaves, Transfer/Storage/Logging Containers, and Sampling Manifolds").
If H2S is released, the immediate area is evacuated until the air is tested.
Downhole tools that return core/gas/liquid under pressure must comply with the following.
All pressure corers and pressurized transfer/storage/logging containers must have a written operator's manual that has been submitted to and approved by ODP and the ship operator's management prior to deploying the tool on the JOIDES Resolution. The manual must not only instruct the user on safe operation of the tool but also clearly state the types of hazards the tool presents to the operator. In regard to the potential release of H2S, the operator must be informed of all potential locations on the tool where pressure containment could fail (seals, valves, rupture disks, etc.).
When a pressure sampler is retrieved on the rig floor, all potential locations for containment failure must be surveyed with a handheld detector.
If the contents of the pressure sampler are transferred to secondary sample chamber or into a manifold/collection system, a handheld detector must be used to monitor the transfer operation.
When operating in a WATCH (H2S potential) or higher H2S hazard condition, then it must be assumed that the pressure sampler or transfer/storage/logging container contains H2S until the trapped gases can be sampled and determined otherwise. The following applies to both pressure samplers and transfer containers: