H2S HAZARD CONDITIONS

There are five H2S hazard conditions, excluding "normal operations" (Table T1). This manual provides a minimum set of guidelines for each hazard condition covering the following topics:

The H2S hazard condition is set by the offshore installation manager based on the concentration of H2S (ppm) in air, the type of H2S source, the location of the detector (open air or confined space), and the relative distance of the detector from the H2S source.

Table T1. Hydrogen sulfide operating conditions.
H2S condition
H2S (ppm) measured from
Danger to life
Action
Open air
Core/Drill string
Normal operations No H2S potential
None None
Watch Potential H2S
None Monitor
Alert 1–19 NA None Monitor, use BAs as needed
Danger 20–49 >20 Moderate Stop coring operations
Emergency >50 NA Extreme Evacuate to safe areas

Notes: BA = fixed or portable self-contained breathing system. NA = not applicable.

Common H2S Sources

The most common H2S sources (see "Appendix B") on the JOIDES Resolution are

In all these cases (except for clathrates and blowout situations), the source of H2S is small in volume or must pass through a small opening first (i.e., the open end of the drill string) before reaching a work area.

H2S Detectors

Fixed-Area Detection Stations

Fixed-area detection stations are mounted around the ship (see "Appendix A") where H2S sources are present or in areas where H2S may accumulate. One or two sensors can be attached to each detection station. The stations are mounted in open areas and continuously monitor for H2S in the work area atmosphere. The detection stations are connected via radio to an alarm control panel mounted on the ship's bridge. In addition, each station may have either an audio or a visual alarm, or both.

All fixed H2S sensors are set to detect a minimum of 10 ppm. Warning lights and horn units are installed on each detector station. If H2S is present at concentrations at or above 10 ppm, a local audible and visual alarm will sound in the hazardous area where H2S is detected. At the same time, an audible and visual alarm will be triggered on the central alarm panel on the bridge.

For detailed operating instructions and specifications, see the manufacturer's operator manual.

Portable Detectors

The staff on the rig floor and core-receiving platform use handheld portable detectors to spot check for the presence of H2S. In addition, this style of detector can be used to monitor the work atmosphere.

Personal Detectors

Staff wear personal detectors while working directly with potential H2S sources.

H2S Hazard Determination

To determine the level of the H2S hazard (see "Appendix C"), it is important to remember the following facts:

The following examples demonstrate why it is important to understand where and how H2S was detected before assigning a hazard classification.

In the first example, the H2S level measured at the detector has been reduced by distance. It is possible that the concentration of H2S near the open drill string is at a lethal level. In an open-air location, a fixed detector cannot be used as the primary means of H2S detection. However, the detection of any H2S by a fixed detector in an open-air location could indicate a very serious condition near the source. When a fixed detector is activated in an open-air setting, personnel not wearing a portable breathing apparatus (BA) must leave the work area immediately until the source has been discovered (using a portable detector) and the concentration of H2S has dropped to a safe level.

In the second example, the H2S measurement was taken directly at the source in a confined space. Because the staff working on the core-receiving platform are in an open-air environment, a measurement should be taken 12 in away from the core to determine the actual hazard level. If this measurement shows an H2S level >20 ppm, then BAs are only needed for individuals working directly over the core; other individuals working on the core-receiving platform do not need to wear a BA.

The third example is a serious situation because the detector is monitoring a confined space. Only individuals wearing BAs should enter this area to begin ventilation. Note, however, that H2S readings taken in a confined space should not necessarily be used to determine H2S hazard conditions for the entire ship.

H2S Hazard Responsibilities

Offshore Installation Manager

Night Tool Pusher

ODP Operations Manager

Ship's Master and Officers

When an H2S emergency (>50 ppm) condition is encountered, the ship's master or ship's officer on duty is solely responsible for determining what action is required and, as necessary, sounding the general alarm to notify personnel to report to the designated safe-briefing area.

The ship's master or officer

Laboratory Officer

Assistant Laboratory Officer

Ship's Department Supervisor

Core Technician

H2S Safety Technician

Ship's Physician

All Personnel

All personnel working in the designated hazardous areas (rig floor, core-receiving platform, core laboratory, and reefer) must

NEXT